§ 14.90.070. Inspection requirements.


Latest version.
  • The building official shall require only one section for small residential rooftop solar energy systems eligible for expedited review as provided by this chapter. Such inspection shall be performed in a timely manner. If the small rooftop solar energy system fails the single inspection, subsequent inspections shall be authorized.

    (Ord. No. 7267, § 2, 10-5-2015)

    TITLE 14 FOOTNOTES

    1.

    For statutory provisions authorizing cities to adopt codes by reference, see Gov. Code § 50022.1 et seq.; for the state law adopting building codes and other codes to apply as housing construction regulations throughout the state, see Health & Saf. Code § 17922.

    1A.

    Prior ordinance history: Ords. 5471, 5550, 5568 and 6301.

    3.

    For statutory provisions requiring municipal health officers to prevent spread of contagious diseases, see Health & Saf. Code § 3110 et seq.

    APPENDIX A

    TABLE 15-D-1-ROOFING TILE APPLICATION FOR ALL TILES

    ROOF SLOPE 2 ½ UNITS VERTICAL IN 12 UNITS HORIZONTAL (21% SLOPE) TO LESS THAN 3 UNITS VERTICAL IN 12 UNITS
    HORIZONTAL (25% SLOPE)
    ROOF SLOPE 3 UNITS VERTICAL IN 12 UNITS HORIZONTAL (25% SLOPE) AND OVER
    1. Deck Requirements Solid sheathing per Sections 2312.2 and 2320.12.9 Solid sheathing per Sections 2312.2 and 2320.12.9
    2. UNDERLAYMENT
    In climate areas subject to wind-driven snow, roof ice damming or special wind regions as shown in Chapter 16, Figure 16-1. Built-up roofing membrane, three piles minimum, applied per Section 1507.6. Surfacing not required. Same as for other climate areas, except that extending from the eaves up the roof to a line 24 inches (610 mm) inside the exterior wall line of the building, two layers of underlayment shall be applied shingle fashion and solidly cemented together with an approved cementing material.
    Other climate areas Built-up roofing membrane, three piles minimum, applied per Section 1507.6. Surfacing not required.
    3. Attachment
    Type of fasteners Hot dipped galvanized ring shank or other approved corrosion-resistant nails not less than No. 11 gage, 5/16 inch (7.9 mm) head. Fasteners shall comply with the requirements of Chapter 23, Division III, Part III. Fasteners shall be long enough to penetrate into the sheathing ¾ inch (19 mm) or through the thickness of the sheathing, whichever is less. Attaching wire for clay or concrete tile shall not be smaller than 0.083 inch (2.11 mm) (No. 14 B.W. gage) and be of copper, brass or stainless steel. Hot dipped galvanized ring shank or other approved corrosion-resistant nails not less than No. 11 gage, 5/16 inch (7.9 mm) head. Fasteners shall comply with the requirements of Chapter 23, Division III, Part III. Fasteners shall be long enough to penetrate into the sheathing ¾ inch (19 mm) or through the thickness of the sheathing, whichever is less. Attaching wire for clay or concrete tile shall not be smaller than 0.083 inch (2.11 mm) (No. 14 B.W. gage) and be of copper, brass or stainless steel.
    Number of fasteners 2,3 Two fasteners per tile. Two fasteners per tile
    4. Tile headlap 3 inches (76 mm) minimum. 3 inches (76 mm) minimum.
    5. Flashing Per Sections 1508.4 and 1509. Per Sections 1508.4 and 1509.

     

    1 In snow areas, a minimum of two fasteners per tile are required.

    2 In areas designated by the building official as being subject to repeated wind velocities in excess of 80 miles per hour (129 km/h) or where the roof height exceeds 40 feet (12 192 mm) above grade, all tiles shall be attached as follows:

    2.1 The heads of all tiles shall be nailed.

    2.2 The noses of all eave course tiles shall be fastened with approved clips.

    2.3 All rake tiles shall be nailed with two nails.

    2.4 The noses of all ridge, hip and rake tiles shall be set in a bead of approved roofer's mastic.

    3 In snow areas, a minimum of two fasteners per tile are required, or battens and one fastener.

    4 On slopes over 24 units vertical in 12 units horizontal (200% slope), the nose end of all tiles shall be securely fastened.

    5 Underlayment shall comply with ASTM D 226-97.

    APPENDIX B

    TABLE 15-D-2

    CLAY OR CONCRETE ROOFING TILE APPLICATION
    INTERLOCKING TILE WITH PROJECTING ANCHOR LUGS—
    MINIMUM ROOF SLOPE 4 UNITS VERTICAL
    IN 12 UNITS HORIZONTAL (33.3% SLOPE)

    ROOF SLOPE 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL (33.3% SLOPE) AND OVER
    1. Deck requirements Per Table 15-D-1
    2. Underlayment
    In climate areas subject to wind-driven snow, roof, ice or special wind regions as shown in Chapter 16, Figure 16-1. Solid sheathing one layer of Type 30 felt lapped 3 inches (76 mm) horizontally and 6 inches (152 mm) vertically, except that extending from the eaves up the roof to line 24 inches (610 mm) inside the exterior wall line of the building, two layers of the underlayent shall be applied shingle fashion and solid cement together with approved cementing material.
    Other climates For solid sheathing, one layer of Type 30 felt lapped 3 (76 mm) horizontally and 6 inches (152 mm) vertically.
    3. Attachment
    Type of fasteners Hot dipped galvanized ring shank or other approved corrosion resistant nails not less than No. 11 gage, 5/16 inch (7.9 mm) head. Fasteners shall comply with the requirements of Chapter 23, Division III, Part III. Fasteners shall be long enough to penetrate through the battens and into sheathing ¾ inch (19 mm) or through the thickness of the sheathing, whichever is less. Attaching wire for clay or concrete tile shall not be smaller than 0.083 inch (2.11 mm) (No. 14 B.W. gage). Horizontal battens are required on solid sheathing for slopes 7 units vertical in 12 units horizontal (58.3% slope) and over. Horizontal battens are required for slopes over 7 units vertical in 12 units horizontal (58.3% slope).
    No. of fasteners One fastener per tile.
    4. Tile headlap 3-inch (76 mm) minimum
    5. Flashing Per Sections 1508.4 and 1509.

     

    1 In areas designated by the building official as being subject to repeated wind velocities in excess of 80 miles per hour (129 km/h) or where the roof height exceeds 40 feet (12 192 mm) above grade, all tiles shall be attached as set forth below:

    1.1 The heads of all tiles shall be nailed.

    1.2 The noses of all eave course tiles shall be fastened with a special clip.

    1.3 All rake tiles hall be nailed with two nails.

    1.4 The noses of all ridge, hip and rake tiles shall be set in a bead of approved roofer's mastic.

    2 Battens shall not be less than 1-inch-by-2-inch (25 mm by 51 mm) nominal. Provisions shall be made for drainage beneath battens by a minimum of 1/8 -inch (3.2 mm) risers at each nail or by 4-foot-long (1219 mm) battens with at least ½-inch (12.7 mm) separation between battens. Battens shall be fastened with approved fasteners spaced at not more than 24 inches (610 mm) on center.

    3 In snow areas, a minimum of two fasteners per tile are required, or battens and one fastener.

    4 Slopes over 12 units vertical in 12 units horizontal (100% slope), nose ends of all tiles must be securely fastened. Nails must be ½″ (13 mm) from the edge of the batten.

    APPENDIX C

    TABLE 16-N

    STRUCTURAL SYSTEMS

    BASIC STRUCTURAL SYSTEM LATERAL-FORCE-RESISTING SYSTEM
    DESCRIPTION
    R Ω HEIGHT LIMIT FOR SEISMIC ZONES 3 AND 4 (feet) x 304.8 for mm
    1. Bearing wall system 1. Light-framed walls with shear panels
    a. Wood structural panel walls for structures three stories or less 5.5 2.8 65
    b. All other light-framed walls 4.5 2.8 65
    2. Shear walls
    a. Concrete 4.5 2.8 160
    b. Masonry 4.5 2.8 160
    3. Light steel-framed bearing walls with tension-only bracing 2.8 2.2 65
    4. Braced frames where bracing carries gravity load
    a. Steel 4.4 2.2 160
    b. Concrete 2.8 2.2 -
    c. Heavy timber 2.8 2.2 65
    2. Building frame system 1. Steel eccentrically braced frame (EBF) 7.0 2.8 240
    2. Light-framed walls with shear panels.
    a. Wood structural panel walls for structures three stories or less 6.5 2.8 65
    b. All other light-framed walls 5.0 2.8 65
    3. Shear walls
    a. Concrete 5.5 2.8 240
    b. Masonry 5.5 2.8 160
    4. Ordinary braced frames
    a. Steel 5 2 35
    b. Concrete 5.6 2.2 -
    c. Heavy timber 5.6 2.2 65
    5. Special concentrically braced frames
    a. Steel 6.4 2.2 240
    3. Moment-resisting frame 1. Special moment-resisting frame (SMRF)
    system a. Steel 8.5 2.8 N.L.
    b. Concrete 8.5 2.8 N.L.
    2. Masonry moment-resisting wall frame (MMRWF) 6.5 2.8 160
    3. Intermediate moment-resisting frame (IMRF)
    a. Steel 4.5 2.8 35
    b. Concrete 5.5 2.8 -
    4. Ordinary moment-resisting frame (OMRF)
    a. Steel 3.5 2.8 35
    b. Concrete 3.5 2.8 -
    5. Special truss moment frames of steel (STMF) 6.5 2.8 240
    4. Dual systems 1. Shear walls
    a. Concrete with SMRF 8.5 2.8 N.L.
    b. Concrete with steel OMRF (Not Permitted) 4.2 2.8 160
    c. Concrete with concrete IMRF 6.5 2.8 160
    d. Masonry with SMRF 5.5 2.8 160
    e. Masonry with steel OMRF (Not Permitted) 4.2 2.8 160
    f. Masonry with concrete IMRF 4.2 2.8 -
    g. Masonry with masonry MMRWF 6.0 2.8 160
    2. Steel EBF
    a. With steel SMRF 8.5 2.8 N.L.
    b. With steel OMRF (Not Permitted) 4.2 2.8 160
    3. Ordinary braced frames (Not Permitted)
    a. Steel with steel SMRF 6.5 2.8 N.L.
    b. Steel with steel OMRF 4.2 2.8 160
    c. Concrete with concrete SMRF 6.5 2.8 -
    d. Concrete with concrete IMRF 4.2 2.8 -
    4. Special concentrically braced frames
    a. Steel with steel SMRF 7.5 2.8 N.L.
    b. Steel with steel OMRF (Not Permitted) 4.2 2.8 160
    5. Steel IMRF (Not permitted)
    5. Cantilevered column building systems 1. Cantilevered column elements 2.2 2.0 35
    6. Shear wall-frame interaction systems 1. Concrete 5.5 2.8 160
    7. Undefined systems See Section 1629.6.7 and 1629.9.2 - - -

     

      N.L.- no limit

    1 See Section 1630.4 for combination of structural systems.

    2 Basic structural systems are defined in Section 1629.6.

    3 Prohibited in Seismic Zones 3 and 4.

    4 Includes precast concrete conforming to Section 1921.2.7.

    5 Prohibited in Seismic Zones 3 and 4, except as permitted in Section 1634.2.

    6 In Seismic Zones 3 and 4 steel IMRF, OMRF and Ordinary Braced Frames are permitted as follows:

    6.1 Steel IMRF and OMRF are permitted, provided the dead load of the floors, walls or roof does not exceed 35 psf respectively and 35 ft. or less in height. Steel IMRF and OMRF are permitted for single-story buildings 60 ft or less in height where the moment joints of field connections are constructed of bolted end plates, provided the dead load of the walls or roof does not exceed 15 psf respectively.

    6.2 Steel Ordinary Braced Frames are permitted for single-story buildings 60 ft or less in height, provided the dead load of the roof does not exceed 15 psf.

    7 Total height of the building including cantilevered columns.

    8 Prohibited in Seismic Zones 2A, 2B, 3 and 4. See Section 1633.2.7.

    APPENDIX D

    Table 23-II-I-1 of the California Building Code is amended to read as follows:

    TABLE 23-II-I-1

    ALLOWABLE SHEAR FOR WIND OR SEISMIC FORCES
    IN POUNDS PER FOOT FOR WOOD STRUCTURAL PANEL
    SHEAR WALLS WITH FRAMING OF DOUGLAS FIR-LARCH
    OR SOUTHERN PINE 1, 2

    Panel Grade Minimum Nominal Panel Thickness (inches) × 25.4 for mm Minimum Nail Penetration in Framing (inches) × 25.4 for mm Allowable Shear Seismic Forces 3, 6, 7 Panels Applied Directly to Framing: NAIL SIZE (Common or Galvanized Box) Allowable Shear Seismic Forces 3, 6, 7 Panels Applied Directly to Framing: Nail Spacing at Plywood Panel Edges (In.) × 25.4 for mm 6 × 0.0146 for N/mm Allowable Shear Seismic Forces 3, 6, 7 Panels Applied Directly to Framing: Nail Spacing at Plywood Panel Edges (In.) × 25.4 for mm 4 × 0.0146 for N/mm Allowable Shear Seismic Forces 3, 6, 7 Panels Applied Directly to Framing: Nail Spacing at Plywood Panel Edges (In.) × 25.4 for mm 3 × 0.0146 for N/mm Allowable Shear Seismic Forces3, 6, 7 Panels Applied Directly to Framing: Nail Spacing at Plywood Panel Edges (In.) × 25.4 for mm 2 × 0.0146 for N/mm Allowable Shear Wind Forces Panels Applied Directly TO Framing: Nail Size (Common or Galvanized Box) Allowable Shear Wind Forces Panels Applied Directly TO Framing: Nail Spacing at Plywood Panel Edges (In.) × 25.4 for mm 6 × 0.0146 for N/mm Allowable Shear Wind Forces Panels Applied Directly TO Framing: Nail Spacing at Plywood Panel Edges (In.) × 25.4 for mm 4 × 0.0146 for N/mm Allowable Shear Wind Forces Panels Applied Directly TO Framing: Nail Spacing at Plywood Panel Edges (In.) × 25.4 for mm 3 × 0.0146 for N/mm Allowable Shear Wind Forces Panels Applied Directly TO Framing: Nail Spacing at Plywood Panel Edges (In.) × 25.4 for mm 2 × 0.0146 for N/mm
    Structural I 5/16 1 ¼ 6d 150 200 200 200 6d 200 300 390 510
    3/8 175 200 200 200 230 360 460 610
    7/16 190 295 380 500 255 395 505 670
    15/32 1 ½ 8d 210 320 410 550 8d 280 430 550 730
    15/32 1 5/8 10d 255 380 500 650 10d 340 510 665 870
    C-D, C-C Sheathing, plywood panel siding and other grades covered in U.B.C. Standard 23-2 or 23-3 5/16 130 200 200 200 180 270 350 450
    3/8 1 ¼ 6d 150 200 200 200 6d 200 300 390 510
    3/8 165 200 200 200 220 320 410 530
    7/16 180 260 335 435 240 350 450 585
    15/32 1 ½ 8d 200 285 370 480 8d 260 380 490 640
    15/32 230 345 650 580 310 460 600 770
    19/32 1 5/8 10d 255 380 500 650 10d 340 510 665 870
    NAIL SIZE (Galvanized Casing) NAIL SIZE (Galvanized Casing)
    Plywood panel siding in grades covered in U.B.C. Standard 23-2 5/16 1 ¼ 6d 100 150 200 200 6d 140 210 275 360
    3/8 1 ½ 8d 120 180 200 200 8d 160 240 310 410

     

    1 All panel edges backed with 2-inch (51 mm) nominal or thicker framing. Panels installed either horizontally or vertically. Space nails at 6 inches (152 mm) on center along intermediate framing members for 3/8 -inch (9.5 mm) and 7/16 -inch (11 mm) panels installed on studs spaced 24 inches (610 mm) on center and 12 inches (305 mm) on center for other conditions and panel thicknesses. These values are for short-time loads due to wind or earthquake and must be reduced 25 percent for normal loading.
    Allowable shear values for nails in framing members of other species set forth in Division III, Part III, shall be calculated for all other grades by multiplying the shear capacities for nails in STRUCTURAL I by the following factors: 0.82 for species with specific gravity greater than or equal to 0.42 but less than 0.49, and 0.65 for species with a specific gravity of less than 0.42.

    2 Where panels are applied on both faces of a wall and nail spacing is less than 6 inches (152 mm) on center on either side, panel joints shall be offset to fall on different framing members or framing shall be 3-inch (76 mm) nominal or thicker and nails on each side shall be staggered.

    3 In Seismic Zones 3 and 4, where allowable shear values exceed 300 pounds per foot ( 4.38 N/mm) foundation sill plates and all framing members receiving edge nailing from abutting panels shall not be less than a single 3-inch (76 mm) nominal member and foundation sill plates shall not be less than a single 3-inch (76 mm) nominal member. In shear walls where total wall design shear does not exceed 450 pounds per foot ( 6.94 N/mm), a single 2-inch (51 mm) nominal sill plate may be used, provided anchor bolts are designed for a load capacity of 50 percent or less of the allowable capacity and bolts have a minimum of 2-inch-by-2-inch-by- 3/16 -inch (51 mm by 51 mm by 5 mm) thick plate washers. Plywood joint and sill plate nailing shall be staggered.

    4 The values for 3/8 -inch (9.5 mm) and 7/16 -inch (11 mm) panels applied direct to framing may be increased to values shown for 15/32 -inch (12 mm) panels, provided studs are spaced a maximum of 16 inches (406 mm) on center or panels are applied with long dimension across studs.

    5 Galvanized nails shall be hot-dipped or tumbled.

    6 The maximum allowable shear for three-ply plywood resisting seismic forces is 200 pounds per foot (2.92 kN/m).

    7 Framing at adjoining panel edges shall be 3-inch (76 mm) nominal or thicker and nails shall be staggered where nails are spaced 2 inches (51 mm) on center.

    APPENDIX E

    TABLE 23-IV-C-1

    BRACED WALL PANELS

    Seismic Zone Condition Construction Method 2,3 : 1 Construction Method 2,3 : 2 Construction Method 2,3 : 3 Construction Method 2,3 : 4 Construction Method 2,3 : 5 Construction Method 2,3 : 6 Construction Method 2,3 : 7 Construction Method 2,3 : 8 Braced Panel Location and Length
    0,1 and 2A One story, top of two or three story X X X X X X X X Each end and not more than 25 feet (7620 mm) on center
    First story of two story or second story of three story X X X X X X X X
    First story of three story X X X X X X X
    2B, 3 One story, or top of two story or three story X X X X X X X Each end and not more than 25 feet (7620 mm) on center
    First story of two story or second of three story X X X X X X X Each end and not more than 25 feet (7620 mm) on center but not less than 25% of building length
    First story of three story X X X X X X X Each end and not more than 25 feet (7620 mm) on center but not less than 40% of building length
    4 One-story building x x Each end and not more than 25 feet (7620 mm) on center but not less than 25% of building length for method 3 and 50% for method 7.

     

    1 This table specifies minimum requirements for braced panels which form interior or exterior braced wall lines.

    2 See Section 2320.11.3 for full description.

    3 See Section 2320.11.4 for alternate braced panel requirement.

    4 Building length is the dimension parallel to the braced wall length.

    5 Gypsum wallboard applied to supports at 16 inches (406 mm) on center.

    6 Not permitted for bracing cripple walls in Seismic Zone 4. See Section 2320.11.5.

    7 The required lengths shall be doubled for gypsum bond applied to only one face of a braced wall panel.

    APPENDIX F

    Table 25-I of the California Building Code is amended to read as follows:

    TABLE 25-I

    ALLOWABLE SHEAR FOR WIND OR SEISMIC FORCES IN POUNDS PER
    FOOT FOR VERTICAL DIAPHRAGMS OF LATH AND PLASTER OR
    GYPSUM BOARD FRAME WALL ASSEMBLIES

    Type of Material Thickness of Material × 25.4 for mm × 304.8 for mm Wall Construction Nail Spacing Maximum (inches) × 25.4 for mm Shear Value × 14.6 for N/m Seismic Shear Value × 14.6 for N/m Wind Minimum Nail Size 3, 4 × 25.4 for mm
    1. Expanded metal, or woven wire lath and portland cement plaster 7/8 ″ Unblocked 6 90 180 No. 11 gage, 1 ½″ long, 7/16 ″ head
    2. Gypsum lath 3/8 ″ lath and ½″ plaster Unblocked 5 30 100 No. 13 gage, 1 1/8 ″ long, 19/64 ″ head, plasterboard blued nail
    3. Gypsum sheathing board ½″× 2′ × 8′ Unblocked 4 30 75 No. 11 gage, 1 ¾″ long, 7/16 ″ head, diamond-point galvanized
    ½″ × 4′ Blocked 4 30 175
    ½″ × 4′ Unblocked 7 30 100
    4. Gypsum wallboard or veneer base ½″ Unblocked 7 30 100 5d cooler (0.086″ dia., 1 5/8 ″ long, 15/64 ″ head) or wallboard (0.086″ dia., 1 5/8 ″ long, 9/32 ″ head)
    4 30 125
    Blocked 7 30 125
    4 30 150
    5/8 ″ Unblocked 7 30 115 6d cooler (0.092″ dia., 1 7/8 ″ long, ¼″ head) or wallboard (0.0915″ dia., 1 7/8 ″ long, 19/64 ″ head)
    4 30 145
    Blocked 7 30 145
    4 30 175
    Blocked Base ply: 9 30 250 Base ply -6d cooler (0.092″ dia., 1 7/8 ″ long, ¼″ head) or wallboard (0.0915″ dia., 1 7/8 ″ long, 19/64 ″ head)
    Two ply Face ply: 7 Face ply - 8d cooler (0.113″ dia., 2 3/8 ;long, 9/32 ″ head) or wallboard (0.113″ dia., 2 3/8 ″ long, 3/8 ″ head)

     

    1 These vertical diaphragms shall not be used to resist loads imposed by masonry or concrete construction. See Section 2513.2. Values shown are for short-term loading due to wind or due to seismic loading. Values shown must be reduced 25 percent for normal loading.

    2 Applies to nailing at all studs, top and bottom plates, and blocking.

    3 Alternate nails may be used if their dimensions are not less than the specified dimensions.

    4 This construction shall not be used below the top level of wood construction in a multi-level building.